SAV.200.M
Applications
• HVAC supply or extract air measuring
• Clean room monitoring and control
• Humidifier control
•
• Pool, Greenhouse, Hencoop etc
Features
• Maintenance free
• Humidity accuracy ±2%
• Temperature accuracy 0.3°C
• Operating voltage AC 24 V or DC 14…35 V
• Calibrated and temperature compensated measuring
• Fixed or field selectable output types
• Simple and fast mounting
• LCD display, 2×12 character
• 2 universal input
• Modbus – RS485 port
• Relay output
• Wi-Fi
Electrical
Power Supply : AC 24V (± %5), 50-60 Hz or DC 14…35 V
Power Consumption : max. 1.5 W
Outputs
4…20 mA, maximum 500 ohm
0…10V DC, minimum 1.000 ohm
Accuracy
Humidity: ±2% rH or ±3% rH
Temperature: 0.3°C
General Data
Sensing Element : Digital micro chip
Media : Air or non-aggressive gasses
Operating Temperature : -25 …+70°C
Storage Temperature : -30 …+85°C
Burst Temperature: 125°C
Connections
Terminals : Pluggable screw terminal
Cable : maximum 1.5 mm2
Cable Gland : M16 or PG9
Protection
enclosure IP65/NEMA4
Standards
EMC Directive : EN61326-1
CE Conformity : CE1702_r0
Dimensions
housing : 98.0 x 81.5 x 45.5 mm
probe: 12 (diameter) x 255 (lenght) mm
Weight (packed)
398 gr
SHD.—
product description
Sense Humidity transmitter, Room type
SHD.A–
‘A’ stands for accuracy
2: %2 rH
3: %3 rH
SHD.Axy
‘xy’ stands for output selection
(x:output1, y:output2, both have same property)
0: no output
1: 0…10V
2: 2…10V
3: 0…5V
4: 1…5V
5: 4…20mA
F: field selectable, 0…10V/4…20mA
SHD.Axy.z
‘z’ stands for options
(add each letter that fits your need, no option no addition)
M: Modbus RS485
R: Relay output
W: Wi-Fi (under development)
P: PID output
1: 1 universal input
2: 2 universal inputs
Flyer
Datasheet
Manual
Modbus Manual
.
There are yet no reviews for this product.